UPS2000-A-(6 kVA-10 kVA) 
User Manual 
 
Copyright © Huawei Technologies Co., Ltd. 
 
Table 3-4 Rated voltages and currents for backfeed protection contactors 
Rated Voltage and Current 
Recommended 
Contactor Model 
220, 230, or 240 V AC, 40 A 
LC1-D40A (Schneider 
contactor) 
208, 220, 230, or 240 V AC, 40 A 
 
Single-phase: 
LC1-D40A (Schneider 
contactor) 
 
Dual-live-wire: 
AF50-30-11*70 (ABB) 
220, 230, or 240 V AC, 65 A 
LC1-D50A (Schneider 
contactor) 
208, 220, 230, or 240 V AC, 65 A 
 
Single-phase: 
LC1-D50A (Schneider 
contactor) 
 
Dual-live-wire: 
AF50-30-11*70 (ABB) 
 
Table 3-5 Control relay parameters 
HF18FF/012 (HONGFA control relay) 
Dry contact: NC 
Breaking capability: 250 V AC, 5 A 
Coil: 12 V rated voltage; rated current of 
less than 1 A 
MY2N-J DC12V (OMRON control relay) 
HJ2-L-DC12V (Panasonic control relay) 
 
3.4.2 Feedback Prevention Connections (With Dry Contract 
Control) 
Figure 3-25 and Figure 3-26 show backfeed protection connections (with dry contract 
control).