UPS2000-A-(6 kVA-10 kVA) 
User Manual 
9 Technical Specifications 
 
Copyright © Huawei Technologies Co., Ltd. 
 
6 kVA/10 
kVA 
Standard 
Version with 
Standard 
Backup Time 
6 kVA/10 
kVA 
Standard 
Version 
with Long 
Backup 
Time 
6 kVA/10 
kVA 
Professional 
Version 
with 
Standard 
Backup 
Time 
6 kVA/10 
kVA 
Professional 
Version 
with Long 
Backup 
Time 
 
Normal mode, 105%–125% load: The UPS transfers to bypass 
mode in 5 minutes if the bypass is normal or disconnects the 
output if the bypass is abnormal. 
 
Normal mode, 125%–150% load: The UPS transfers to bypass 
mode in 1 minute if the bypass is normal or disconnects the 
output if the bypass is abnormal. 
 
Normal mode, ≥ 150% load: The UPS transfers to bypass mode 
in 0.2 second if the bypass is normal or disconnects the output 
if the bypass is abnormal. 
Dynamic voltage 
transient 
Average frequency 
tracking rate 
0.5–2 Hz/s for a single UPS 
 
9.6 Battery Electrical Specifications 
UPS2000-A-6 
kVA/10 kVA 
Standard 
Version 
with 
Standard 
Backup 
Time 
UPS2000-A-6 
kVA/10 kVA 
Standard 
Version 
with Long 
Backup 
Time 
UPS2000-A-6 
kVA/10 kVA 
Professional 
Version 
with 
Standard 
Backup 
Time 
UPS2000-A-6 
kVA/10 kVA 
Professional 
Version 
with Long 
Backup 
Time 
6 kVA standard version with standard backup time: contains 
sixteen 7 Ah, 12 V lead-acid batteries; 10 kVA standard version 
with standard backup time: contains sixteen 9 Ah, 12 V lead-acid 
batteries; 6 kVA professional version with standard backup time: 
contains twenty 7 Ah, 12 V lead-acid batteries; 10 kVA 
professional version with standard backup time: contains twenty 9 
Ah, 12 V lead-acid batteries; UPS with long backup time: connects 
to external battery boxes and supports 16–20 batteries