UPS2000-A-(6 kVA-10 kVA) 
User Manual 
 
Copyright © Huawei Technologies Co., Ltd. 
 
Step 2  Perform "shutdown operations" on each UPS in the parallel system. All inverters shut down at 
the same time, and the parallel system transfers to bypass mode. 
Step 3  Switch off the following circuit breakers in sequence: the upstream AC input circuit breaker 
of each UPS, the AC input circuit breaker at the rear of each UPS, the general AC input 
circuit breaker of the parallel system, the AC output circuit breaker of each UPS, and the 
general AC output circuit breaker of the parallel system. After all indicators turn off and fans 
stop, the UPS shuts down and stops supplying power to loads. 
Step 4  (This step is required only for the UPS with long backup time.) If the battery circuit has a 
circuit breaker, switch off the external battery circuit breaker. If the battery circuit does not 
have a circuit breaker, disconnect battery cables. 
----End 
5.3.3 Performing EPO for a Parallel System 
Turn on the EPO switches (provided by the customer). The UPSs enter the EPO state. That is, 
the UPSs shut down the inverters, and do not transfer to bypass mode. 
Figure 5-39 shows the EPO cable connection On a parallel system. 
Figure 5-39 EPO cable connection on a parallel system 
 
 
 
 
Connect an external switch to the EPO port and turn on the switch. After you turn on the switch, the 
inverter stops, and the UPS does not transfer to bypass mode. In this way, the UPS stops supplying 
power immediately. 
 
The external switch (switch or dry contact signals controlled by a switch) is provided by the 
customer. 
 
After UPSs enter the EPO state, a 55-1 EPO alarm is generated. After the EPO is cleared, choose 
CTR > ALR CLR clears the automatically detected and manually cleared (ADMC)    alarms on 
LCD, as shown in Figure 5-40.