UPS2000-A-(6 kVA-10 kVA) 
User Manual 
 
Copyright © Huawei Technologies Co., Ltd. 
 
Table 4-1 Indicator description 
The UPS is in normal mode. 
The UPS is not in normal mode. 
The UPS is in battery mode. 
The UPS is not in battery mode. 
The remaining battery capacity is less 
than 25%. 
The UPS is in bypass mode. 
The UPS is not in bypass mode. 
The UPS generates an critical alarm. 
The UPS generates an minor alarm. 
The UPS is running properly. 
 
 
The UPS is in ECO mode when the mains indicator and bypass indicator are both on. 
4.3 Functional Buttons 
The control panel provides four buttons to start and shut down the UPS and set parameters. 
Table 4-2 describes the buttons. 
Table 4-2 Button description 
 
On the default screen, press ESC for more than 5 
seconds. Release the button when you hear a 
beep sound. The inverter shuts down. 
 
On any other screen, press ESC to return to the 
upper-level menu (the default screen is the 
upper-level screen for the main menu screen). 
Press ▲ or ▼ to scroll upward or downward. 
You can set a value by using the list or step increase 
or decrease. 
Enter/Startup/Battery 
Self-Check/Mute 
 
On the default screen in bypass mode, hold 
down    for more than 5 seconds. Release 
the button when you hear a beep sound. The 
UPS starts.