UPS2000-A-(6 kVA-10 kVA) 
User Manual 
 
Copyright © Huawei Technologies Co., Ltd. 
 
current of the battery 
string as well as the 
voltage of each battery. 
3.  Check the battery surface 
temperature. 
4.  Keep deformed and 
bulged faulty batteries 
still for 30 minutes and 
then check and record 
open-circuit voltage of 
the faulty battery. 
5.  If the fault persists, 
contact Huawei technical 
support. 
Battery operating 
temperature 
1.  The service temperature 
of a working battery 
does not exceed 45ºC. 
2.  The battery ambient 
temperature is 25±5°C. 
1.  Identify the cause of the 
abnormal battery 
operating temperature. 
2.  If the fault persists, 
contact Huawei technical 
support. 
Parameters settings of 
battery capacity, battery 
number, battery charge 
current limit setting values 
meet requirements and 
match the actual value. 
Tightness of bolts on battery 
terminals 
Battery terminals and cables 
are in good contact. (A 
torque wrench is used for 
checking the contact) 
Tighten the terminals and 
ensure that battery terminals 
and cables are in good 
contact. 
 
Equalized charging 
voltage: 14.1 V/cell ± 0.1 
V/cell 
 
Float charging voltage: 
13.5 V/cell ± 0.1 V/cell 
1.  Check whether the 
equalized charging 
voltage and float 
charging voltage of a 
battery is normal. 
2.  If the charging voltage of 
a battery exceeds the 
specifications 
requirement, perform a 
complete forcible 
equalized charging for 
the battery, and check 
again whether the 
voltage is normal. 
3.  If the fault persists, 
contact Huawei technical 
support.