The number of batteries set on the LCD for the UPS with long backup time should be 
consistent with the actual number. If batteries are added or removed, change the related 
parameters on the LCD accordingly. The battery lifespan will be shortened if the value on the 
LCD is less than the actual number, or a battery leakage or even a fire disaster may occur if 
the value is greater. 
 
 
 
The parameter values in the screenshots are for reference only. Set the parameters as 
required. 
 
Set the voltage level and frequency based on the rated voltage and frequency. In the case 
of single-phase output, set the voltage level to 208 V, 220 V (default), 230 V, or 240 V. 
 
Battery parameters are configurable for the UPS with long backup time in non-battery 
mode or non-battery ECO mode. 
 
Set the number of batteries based on the actual battery quantity.    Professional version 
with standard backup time: 20 batteries; standard version with standard backup time: 16 
batteries, not configurable. UPS with long backup time: 16 batteries by default; value 
range: 16–20.   
 
Set the battery capacity to the total capacity of all batteries actually connected. The value 
is 7 Ah for the 6 kVA UPS with standard backup time and cannot be changed. The value is 
9 Ah for the 10 kVA UPS with standard backup time and cannot be changed. The default 
value is 40 Ah for the 6 kVA UPS with long backup time. The default value is 65 Ah for 
the 10 kVA UPS with long backup time, and the value can range from 7 Ah to 999 Ah. 
 
To set parameters, tap    on the parameter settings screen, press ▲ or ▼, and press    to 
confirm the setting. 
Starting the UPS in Normal Mode 
Step 1  (This step is required only for the UPS with long backup time.) If the battery circuit has a 
circuit breaker, switch on the external battery circuit breaker. If the battery circuit does not 
have a circuit breaker, connect battery cables. 
Step 2  Close the UPS upstream AC input circuit breaker and the AC input circuit breaker on the rear 
panel of the UPS. 
Step 3  After the LCD screen lights up for 1s, the initialization screen is displayed. After the progress 
bar is complete, the default screen is displayed, as shown in Figure 5-1.