UPS2000-A-(6 kVA-10 kVA)
User Manual
9 Technical Specifications
Copyright © Huawei Technologies Co., Ltd.
124
Item
6 kVA/10
kVA
Standard
Version with
Standard
Backup Time
6 kVA/10
kVA
Standard
Version
with Long
Backup
Time
6 kVA/10
kVA
Professional
Version
with
Standard
Backup
Time
6 kVA/10
kVA
Professional
Version
with Long
Backup
Time
Overload capacity
Normal mode, 105%125% load: The UPS transfers to bypass
mode in 5 minutes if the bypass is normal or disconnects the
output if the bypass is abnormal.
Normal mode, 125%150% load: The UPS transfers to bypass
mode in 1 minute if the bypass is normal or disconnects the
output if the bypass is abnormal.
Normal mode, ≥ 150% load: The UPS transfers to bypass mode
in 0.2 second if the bypass is normal or disconnects the output
if the bypass is abnormal.
Dynamic voltage
transient
±5%
Average frequency
tracking rate
0.52 Hz/s for a single UPS
9.6 Battery Electrical Specifications
Item
UPS2000-A-6
kVA/10 kVA
Standard
Version
with
Standard
Backup
Time
UPS2000-A-6
kVA/10 kVA
Standard
Version
with Long
Backup
Time
UPS2000-A-6
kVA/10 kVA
Professional
Version
with
Standard
Backup
Time
UPS2000-A-6
kVA/10 kVA
Professional
Version
with Long
Backup
Time
Rated battery voltage
192 V DC
192 V
DC240 V
DC
240 V DC
192 V
DC240 V
DC
Number of batteries
6 kVA standard version with standard backup time: contains
sixteen 7 Ah, 12 V lead-acid batteries; 10 kVA standard version
with standard backup time: contains sixteen 9 Ah, 12 V lead-acid
batteries; 6 kVA professional version with standard backup time:
contains twenty 7 Ah, 12 V lead-acid batteries; 10 kVA
professional version with standard backup time: contains twenty 9
Ah, 12 V lead-acid batteries; UPS with long backup time: connects
to external battery boxes and supports 1620 batteries
Leakage current
≤ 500 μA

Table of Contents