EasyManuals Logo

Huawei UPS2000-A Series User Manual

Huawei UPS2000-A Series
160 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #147 background imageLoading...
Page #147 background image
UPS2000-A-(6 kVA-10 kVA)
User Manual
B Alarm Handling
Copyright © Huawei Technologies Co., Ltd.
140
Alarm
Name
Alarm
Identifier
(Alarm ID)
WebUI
Decimal
System
Alarm
Identifier
(Alarm ID)
LCD
Heuristicim
al System
Alarm
level
Alarm
Clear
Mode
Impact on
the System
Repair Proposal
fault
-off clear
transfers to
another
working
mode.
damaged.
Measure: Contact
Huawei technical
support.
Internal
fault
2A-0F
42-15
Critical
Manual
clear/Power
-off clear
The UPS
cannot start.
Possible cause: The
rectifier circuits are
damaged.
Measure: Contact
Huawei technical
support.
Internal
fault
2A-11
42-17
Critical
Manual
clear/Power
-off clear
The UPS
shuts down or
transfers to
another
working
mode.
Possible cause: The
mains has
experienced a
transient high
voltage.
Measure: Rectify the
fault and restart the
UPS.
Possible cause: The
output supplies
power to special
loads such as the
inductive and
rectification loads.
Measure: Check that
the load types are
supported by the
UPS.
Possible cause: The
hardware is
damaged.
Measure: Contact
Huawei technical
support.
Internal
fault
2A-12
42-18
Critical
Manual
clear/Power
-off clear
The UPS
shuts down or
transfers to
another
working
mode.
Possible cause: The
hardware is
damaged.
Measure: Contact
Huawei technical
support.
Possible cause: An
overload occurred
when the input

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Huawei UPS2000-A Series and is the answer not in the manual?

Huawei UPS2000-A Series Specifications

General IconGeneral
BrandHuawei
ModelUPS2000-A Series
CategoryUPS
LanguageEnglish

Related product manuals