4 — Installation
Installation Options
VERSA-TECH
®
single-phase reclos-
ers are designed for outdoor pole or
structure mounting and application on
overhead electrical distribution systems.
The energized recloser is insulated from
the pole/structure by a polymer insulator.
The VERSA-TECH
®
Single Phase Elec-
tronic Recloser is available in two basic
mounting configurations:
1. Pole/Structure mounting (see Fig. 4-1)
2. Crossarm mounting (see Fig. 4-2).
Refer to the catalog number of the unit. The
fourth (4th) character position indicates
the mounting arrangement, e.g., the "1" in
the seventh position of (PSC86)2X11XXX
indicates a Pole/ Structure mounting. A “2” in
this position indicates Crossarm mounting,
e.g., (PSC86)2X12XXX.
Figure 4-6 Pole/Structure Mounting
Figure 4-7 Crossarm Mounting
Figure 4-8 Bypass Arrangement
Hubbell Power Systems recommends the
use of a by-pass switch in parallel with the
recloser. This arrangement allows the unit to
be easily taken out of the circuit for service,
should the need arise. It also allows all
connections to be made without picking up
load current with the jumper connections
(see Fig. 4-3).
LIGHTNING ARRESTERS NOTE:
Hubbell Power Systems recommends
placing appropriately rated lightning
arresters as close as possible on both
the source and load sides of the recloser.
(Refer to Ohio Brass catalog.)