ADVANCED FEATURES (CONTINUED)
Use the ▲ or ▼ buttons and the ◄ and ► buttons to navigate through  
the Custom, K-Factor, and Offset screen. Once you navigate to a number, 
it will ash. The number may be changed by pressing the + / – button to 
either increase or decrease the value. Once you have completed entering 
the K-Factor and Offset specied by the manufacturer of the ow sensor, 
use the ▼ button to return to the main Sensor Conguration screen. 
If an HFS sensor has been selected and programmed in the Sensor 
Conguration screen, the main RUN screen will indicate a ashing ow rate 
anytime a station is irrigating. If the station's ow has not been learned or the 
station has not been enabled for ow monitoring, which will be discussed 
in the Flow Operation and Manual Operation section, the screen will still 
indicate a total ow of 0.0 GPM because the HFS has been selected. 
Flow Operation
The Flow Operation feature allows you to program ow monitoring 
functions for each station. You can program the controller to either monitor 
ow for a station or not monitor ow for a station. 
1. 
 Turn the dial to the ADVANCED FEATURES position. Use the ▲ and 
▼ to select Flow Operation and use the + button to enter. 
2.  Use the ◄ and ► buttons to navigate to the station you would like  
to program. 
3.   The cursor will be displayed next to Monitored. Use the + / – button 
to enable or disable ow monitoring for that station. 
If ow monitoring is enabled (Yes), you will be given the ability to change 
certain characteristics of each stations monitored ow. As soon as the 
station is enabled the new screen will appear with the following selections:
• Expected Flow – the amount of ow expected for that station in 
Gallons Per Minute (GPM )or Liters Per Minute (LPM)
• Overow – Can be set from 110% to 300% of Expected Flow. During 
system operation, if the station ow exceeds the Overow limit, the 
controller will shut the system down and begin diagnostic testing. For 
example, if the expected ow is 20 GPM and the overow is set to 
115%, the actual ow would need to exceed 15% (3 gallons) of the 
expected ow. Therefore, the station would need to exceed 23 GPM 
before the controller would go into overow alarm.
• Underow – Can be set from 10% to 100% of Expected Flow. During 
system operation, if the actual station ow falls below the Underow 
limit, the controller will shut the system down. For example, if the 
expected ow is 20 GPM and the underow is set to 50%, the actual 
ow would need to underow by 50% (10 gallons) of the expected 
ow. Therefore, the station would need to ow at a minimum of 10 
GPM before the controller would go into an underow alarm.
• Start Delay – Can be set from 5 seconds to 10 minutes. The Start 
Delay prevents premature system shutdown due to erratic ow within 
the mainline by providing a delay before the system shutdown occurs. 
It allows the system to stabilize prior to shutting the system down 
during Overow and Underow conditions. 
After the station has been enabled, press the ▼ button to select any of 
the features mentioned above. With the ► cursor pointing to the ow 
characteristic, press the + / – button to increase or decrease the value until 
the desired number is reached. 
If ow monitoring is enabled for a specic station, the factory preset 
values will be displayed. The expected ow will be blank, because the 
actual learning process has not taken place. The learning process will be 
discussed in the Manual Operation, Learn Expected Flow section. Overow 
will be 115%, underow will be 50%, and the preset Start Delay will be set 
to 1 minute. 
Flow Operation is necessary to program in order for the controller to know 
which stations to monitor. Important additional steps that need to be taken 
to complete the ow monitoring setup. A ow sensor needs to be assigned 
in the Sensor Conguration screen, and the stations set to be monitored 
need their ows to be learned. These steps are required in order for ow 
monitoring to occur. 
If a station has been enabled for ow monitoring, it is important to know 
that the System Status Dashboard ow light will become active for that 
station. If the other components to complete the ow monitoring process 
have not been programmed, but the station’s ow has been enabled, the 
System Status Flow light will light Green indicating a normal ow.
A detailed description of what happens in the case of an overow or 
underow is discussed in the controller Diagnostics and Troubleshooting 
section under System Status Dashboard, Flow. It is very important to read 
and understand this description before ow monitoring occurs.
23