10 EDS 300
Status: 19.09.2018 HYDAC ELECTRONIC GMBH Part No.: 669648 E
8.4 SETTING RANGES FOR SWITCHING OUTPUTS
Switching point function
Measuring range
In bar
Switch point
In bar
Hysteresis
In bar
Increment*
In bar
0 .. 16 0.3 .. 16 0.1 .. 15.8 0.1
0 .. 40 0.6 .. 40 0.2 .. 39.6 0.2
0 .. 100 1.5 .. 100 0.5 .. 99.0 0.5
0 .. 250 3.0 .. 250 1.0 .. 248 1.0
0 .. 400 6.0 .. 400 2.0 .. 396 2.0
0 .. 600 15.0 .. 600 5.0 .. 590 5.0
Window function
Measuring range
In bar
Lower switch value
In bar
Upper switch value
In bar
Increment*
In bar
0 .. 16 0.2 .. 15.9 0.3 .. 16 0.1
0 .. 40 0.4 .. 39.8 0.6 .. 40 0.2
0 .. 100 1.0 .. 99.5 1.5 .. 100 0.5
0 .. 250 2.0 .. 249.0 3.0 .. 250 1.0
0 .. 400 4.0 .. 398.0 6.0 .. 400 2.0
0 .. 600 10.0 .. 595.0 15.0 .. 600 5.0
*All ranges given in the table are adjustable by the increments shown.
9 Basic settings
In order to adapt the unit to a particular application, the function of the EDS 300 can be altered via
several basic settings. These are combined in one menu.
9.1 ALTERING THE BASIC SETTINGS
NOTE:
• When the menu is activated no switching operations are carried out.
• Switch off supply voltage or disconnect the unit from the supply voltage.
To close the basic setting menu:
Call up the menu point "END", set to "YES", the EDS 300 returns to the normal display mode after
2 seconds.
NOTE:
• If after about 50 seconds no keys have been pressed, the menu automatically closes
down. Any changes which may have been made will not be saved
(for summary see 8.2)