Installation Manual 5.1.2
11
Figure 5.3 Dual Tank Hot Water Only copper tubing should be utilized (H005673)
C
old Water In
Ball Valve
(Valve A)
Water OUT
Water IN
3/4" Hose Bib
(Boiler Drain
A for Purgin g)
Horizontal Swing
Check Valve
Ball Valve (Valve B)
3/4" Boiler Drain B
(Used to drain tank only)
C
H
C
H
T1
T2
T3
Note: The 3 Tee's
labeled T1, T2 and T3
must be "
centere
d" to
ensure equal flow
from both tanks.
Hot Water Out
BRONZE Circulating
Pump mounted
vertical (Can be
Installed in either
Line)
All pipe fittings in this area MUST be Copper,
brass, bronze or Steel and must extend a
minimum of 12" above the "T" before
connecting to CPVC or PEX
All copper piping must be the same size as the fittings on the Hydro-Temp
system. Under sizing this piping will reduce the gpm flow and can damage
the unit and void the warranty. If 1" copper is used it must be reduced to 3/4"
as close to the tank as possible.
Note: on long piping runs the copper piping may need to be "upsized" to
lower the pressure drop of the circuit.
Dielectric Fittings
Tank Isolation Ball Valves