Other voltages are available on request.
We recommend employing medium blow main fuses (applicable
only to the grid voltages above). See table below indicating max-
imum power usage for each circuit protection:
When using fault current circuit breakers please use a separate
one for the humidifier.
HyLine:
CompactLine:
Type Standard Main Power Supply
HY05 - HY45 1 x 400V/3Phase/N
HY60 - HY116 2 x 400V/3Phase/N
C01, C02 1 x 230/1Phase/N
C06 - C58 1 x 400V/3Phase/N
MS5, MS10 1 x 400V/3Phase/N
MS5 1 x 230/1Phase/N
DBE 2 1 x 230V/1Phase
DBE 6-45 1 x 400V/3Phase/N
Type Power Usage Circuit Protection
HY05 5,4 A 3 x 6A
HY08 8,7 A 3 x 10A
HY13 14,1 A 3 x 16 A
HY17 18,4 A 3 x 20 A
HY23 24,9 A 3 x 35 A
HY30 32,5 A 3 x 35 A
HY45 48,8 A 3 x 63 A
HY60 2 x 32,5 A 6 x 35 A
HY90 2 x 48,8 A 6 x 63 A
HY116 2 x 62,8 A 6 x 63 A
Type Power Usage Circuit Protection
C01 3,3A 1 x 6A
C02 6,5A 1 x 10A
C06 6,5 A 3 x 10 A
C10 10,8 A 3 x 16 A
C17 18,4 A 3 x 20 A
C22 23,8 3 x 35 A
C30 32,5 A 3 x 35 A
C45 48,8 A 3 x 63 A
C58 62,8 A 3 x 63 A