Page 47
Warning: Check the inside of the top part of steam cylinder for
crust build-up and possible salt bridges (black grooves between
the electrode leads). If present, wash away completely .
Note: If electrical arcs have burned deep grooves in the mate-
rial, the top part of the cylinder must be replaced.
Warning: Clean the sensor electrode until it is bright.