EasyManuals Logo

IBC CX Series User Manual

IBC CX Series
124 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #43 background imageLoading...
Page #43 background image
Warning
Fill the trap with water before initially firing the boiler to prevent exhaust fumes from
entering the room. Never operate the boiler unless the trap is filled with water. Failure to
comply will result in severe personal injury or death.
Ensure the supplied trap is correctly
installed and filled with water.
When required, add (and maintain in
good condition) a neutralization tank.
For information on installing a
condensate neutralizer, see Installing
a condensate neutralizer on page 45.
The condensate trap must be installed
on the drain connection at the base of
the boiler. The condensate drain must
be piped to within 1" of a drain or
connected to a condensate pump.
The drainage line must slope down to
the drain at a pitch of ¼" per foot so
condensate runs towards the drain.
43
3.9 Installing a condensate trap

Table of Contents

Other manuals for IBC CX Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the IBC CX Series and is the answer not in the manual?

IBC CX Series Specifications

General IconGeneral
BrandIBC
ModelCX Series
CategoryBoiler
LanguageEnglish

Related product manuals