EasyManuals Logo

IBC CX Series User Manual

IBC CX Series
124 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #46 background imageLoading...
Page #46 background image
Figure 26 Condensate neutralization tank
Flue gas exhaust: condensate, and potentially rain water, flow back from the venting
system.
Air intake piping: Warning - Risk of damage to appliance. Ensure that rain water is
prevented from entering.
Condensate water line: Warning - Risk of damage to appliance. All condensate
discharge lines, including neutralization tank inlet, must be at a lower elevation than the
condensate water line of the appliance.
Free flow of condensate from venting systems and the pressure vessel must be
maintained at all times. Trap and condensate drain piping must be accessible to allow
regular inspection and cleaning.
46
Section: Installation

Table of Contents

Other manuals for IBC CX Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the IBC CX Series and is the answer not in the manual?

IBC CX Series Specifications

General IconGeneral
BrandIBC
ModelCX Series
CategoryBoiler
LanguageEnglish

Related product manuals