EasyManuals Logo

IBC SL 10-85 G3 User Manual

IBC SL 10-85 G3
124 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #44 background imageLoading...
Page #44 background image
intake piping.
Condensate water line.
Warning:Risk of damage to appliance. All condensate discharge lines must be at a lower
elevation than the condensate water line of the appliance.
Affix hose to plastic piping
Factory-supplied condensate trap
Confirm slope. Condensate hose and drain piping to slope toward drain and be secured to
prevent accidental disassembly .
To drain. Drain materials subject to corrosion must be protected by acid neutralization.
Condensate drainage:Free flow of condensate from venting systems and pressure vessel
must be maintained at all times. Trap and condensate drain piping must be accessible to
allow regular inspection and cleaning.
3.10 Installing a condensate neutralizer
If discharging condensate into building drain piping materials that are subject to corrosion, use a
neutralization package.
Caution
After installing a condensate neutralization package, the pH of the condensate
discharge must be measured on a regular schedule to ensure the neutralizing agent is
active and effective.
Danger
The water in the condensate neutralizer can cause severe burns to the skin. Wear
protective gloves and eye wear when servicing the condensate neutralizer.
40
Section: Installation

Table of Contents

Other manuals for IBC SL 10-85 G3

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the IBC SL 10-85 G3 and is the answer not in the manual?

IBC SL 10-85 G3 Specifications

General IconGeneral
BrandIBC
ModelSL 10-85 G3
CategoryBoiler
LanguageEnglish

Related product manuals