EasyManua.ls Logo

ICP C8MPN - Page 24

ICP C8MPN
57 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
24
441 01 2611 06
· Installation of locking-type dampers is recommended in all
branches,orinindividualducts tobalancesystem’sairflows.
· Non--combustible, flexible duct connectors are recom-
mended for return and supply connections to furnace.
· Ifairreturngrilleislocatedclosetothefaninlet,installatleast
one 90° air turn between fan and inlet grille to reduce noise.
· Ductworkinstalledinatticorexposedtooutsidetemperatures
requiresaminimumof2² ofinsulationwithoutdoortypevapor
barrier.
· Ductworkinstalledinanindoorunconditionedspacerequires
a minimum of 1 ² of insulation with indoor type vapor barrier.
Inspection Panel on some models
Forafurnacenotequippedwithacoolingc oil,theoutletductshall
beprovidedwitharemovableaccesspanel. Thisopeningshallbe
accessiblewhenthefurnaceisinstalledandshallbeofs uchasize
thattheheatexchangercanbeviewedforpossibleopeningsusing
light assistance or a probe can be inserted for sampling the air
stream. This access cover shall be attached in such a manner as
to prevent air leaks.
Filters
A filter MUST be used.
Filtersarenotsupplied
withthesefurnaces,butcanbepurchased
from your distributor.
See Table 4 for required high--velocity filter sizes.
Table 4
High--Velocity Air Filter Sizes (max.600 FPM)
Cabinet
Internal Filter External Filter Rack
Width
Bottom Bottom Side+
15
1
/
2
14X25 14X25 14X25 or 16X25
19
1
/
2
16X25* 16X25* 16X25*
22
3
/
4
20X25* 20X25* 16X25*
* Greater than 1600 CFM requires both (left and right) side return filter
racks in upflow position.
+Sidereturnairduct(s)isnotpermittedwithhorizontalordownflowfurnace
installation.
Use either filter type:
· Washable,high--velocityfiltersarebasedonamaximumair
flow rating of 600 FPM.
· Disposable,lowvelocityfiltersarebasedonamaximumair
flow of 300 FPM when used with external filter grille.
!
RISK OF REDUCED FURNACE LIFE
Failure to follow these Caution may result in
premature furnace component failure.
Use of excessively dirty and/or restrictive air filters
may increase furnace operating temperatures and
shorten the life of the furnace.
Filters specified for the furnace are rated at a maximum
of 600 FPM air velocity and sized for the furnace’s
airflow rate. Replacement filters must be of equivalent
type, size, and rating except as described below.
Disposable, low--velocity filters may be used to replace
washable, high--velocity filters, providing they are sized
for 300 FPM or less.
C
A
UTION
· The furnaces with 1600 or less CFM rating use a 16” x 25”
high--velocity filter. On these models the filter may be
mountedinternallyforbottomreturn ora filter and rackmay
be mounted externally for bottom return.
· The furnaces withgreater than 1600 CFM require that both
(left and right) side returns are used. Two side return filters
andracksarerequired.Filterracks mustbemountedexter-
nally. See Figure 24.
· If return air must be on one side only, an optional 20² x25²
filterstandoffrackkitcanbeused.(SeeFigure 22.)Forbot-
tomreturn,aninternalfiltercanbeusedorafilterrackkitcan
be mounted externally.
NOTE:The20 ² x25² standoffs idefilterrackgivesmorefilterarea
but does not provide more air. See Figure 22. To achieve 2000
CFM 2 side returns are still needed. See Figure 24.
NOTE: Disposable low--velocity filters may be replaced with
washable,high--velocityfilters.Washable,high--velocityfilterscan
bereplacedONLYwithsametypeandsizefilterunlesslow--veloc-
ity filters meet the minimum size areas for 300 FPM or less.
Figure 22
Optional Duct Standoff
20x25Optional
Filter Rack
Filter
25--23--05--4
Optional Filter Rack Installation: Side Return
Centerthefilterrackonthesidepanel,flushwiththebottomedge
ofthefurnace. Mark the fastening holes. Drillthe fastening holes
inthes idepanelandfastenthefilterrackinplacewithsheetmetal
screws. See Figure 23 and Figure 24.

Related product manuals