EasyManua.ls Logo

ICP C8MPN - Ductwork and Filter (Upflow;Horizontal)

ICP C8MPN
57 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
23
441 01 2611 06
Fan Control
ThefancontrolispresetatthefactorywithONdelayof30seconds
in the heating mode. The blower OFF timing is preset at 140sec-
onds. If desired,the fan OFF delay can bereset to obtain thelon-
gest delay times while still maintaining comfort levels. See
“Furnace Wiring Diagram”.
Control Center Fuse
The 24V circuit contains a 5--amp, automotive--type fuse located
oncontrolcenter.(SeeFigure 20 )Anyelectricalshortsof24Vwir-
ingduring installation,service,ormaintenancemaycausefuseto
blow. If fuse replacement is required, use only a fuse of identical
size (5 amp.).
Fan Timer Connections
Figure 20
DIP Switch
FUSE
25--23--41
10. Ductwork and Filter (Upflow/Horizontal)
CARBON MONOXIDE POISONING HAZARD.
Failure to properly seal duct could result in death
and/or personal injury.
DoNOT draw returnair from inside a closet or utility
room where furnace is located. Return air duct
MUST be sealed to furnace casing.
!
WARNING
Duct Connections
This furnace may be installed in only a bottom or side return--air
duct application. Return air duct connections through the back of
the furnace is NOT permitted.
Upflow ONLY: Side return--air duct connections can be made by
cutting out the embossed area shown in Figure 21. A plugged
holeisprovidedateachfurnacesideductlocationtohelpstartcut-
tingtheopening. Sideductc onnectionsareNOTpermittedinhori-
zontal flow applications.
Cutting Side Return Air Opening
Figure 21
Plugged
Starting
Hole
Upflow and Horizontal Flow: Bottom return--air duct connec-
tions can be made by removing the knockout panel in thefurnace
base. Do NOT remove knock-out except for a bottom return--air
duct connection.
Duct Design
Designandinstallairdistributionsystemto complywithAirCondi-
tioning Contractors of America manuals or other approved meth-
ods that conform to local codes and good trade practices.
Whenthefurnaceislocatedinanareanearoradjacenttotheliving
area,thesystemshouldbecarefullydesignedwithreturnstomini-
mize noise transmission through the return air grille. Any blower
movingahighvolumeofairwillproduceaudiblenoise,whichcould
beobjectionablewhenthefurnaceislocatedvery closetoaliving
area. It is often advisable to route the return air ducts under the
floor or through the attic.
· Refer to furnace Technical Support Manual (Blower Data)
for air flow information.
· Sizeductworktohandleairflowforheating(andaircondition-
ing if so equipped).
Duct Installation Requirements
· When a furnace is installed so that supply ducts carry aircir-
culated by the furnace to areas outside of the space contain-
ingthefurnace,thereturnairshallalsobehandledby duct(s)
sealed to the furnace casing and terminating outside the
space containing the furnace.
CARBON MONOXIDE POISONING HAZARD.
Failure to follow safety warning exactly could
result in serious injury, d eath, and/or property
damage.
Install cooling coil on furnace discharge. Cool air
passing over heat exchanger could cause conden-
sate to form resulting in heat exchanger failure.
!
W
A
RNING
· Whenthefurnaceisusedwithacoolingunit,thefurnaceshall
beinstalledparallelwithorontheupstreamsideofthecooling
unit to avoid condensation in the heating element.
· Withaparallelflowarrangement,thedampersorothermeans
usedto controlflowofair shallbeadequatetopreventchilled
airfromenteringthefurnace.Chilledairgoingthroughthefur -
nace could cause condensation and shorten furnace life.
Dampers (purchased locally) can be either automatic or
manual. Manuallyorautomatically operateddampersMUST
be equipped with a means to prevent furnace and air condi-
tioningoperation,unlessdamperisinthefullheatorcoolposi-
tion.

Related product manuals