3
Mexico Super RS 3/100 & 3/125 - Installation
Boiler Size RS 3/100 RS 3/125
Gas Supply Connection in. BSP Rc 1/2 (1/2)
Number of Boiler Sections 4 5
Flow and Return Connections Rc 1 (1" BSP)
MAXIMUM Static Water Head m (ft.) 30.5 (100) (3 bar)
MINIMUM Static Water Head m (ft.) 1.0 (3.3)
Electrical Supply 230 V ~ 50 Hz
External Fuse Rating(Power Consumption) 3 A (5 W)
Water Content litre (gal.) 9.8 (2.1) 12.2 (2.7)
Dry Weight kg. (lb.) 113 (249) 136 (300)
Boiler Size Height mm (in.) 850 (33.5)
Width mm (in.) 440. (17.4)
Depth mm (in.) 533 (21.0) 600 (23.6)
Gas Type Natural 2 H
Gas Supply Pressure 20 mb
GENERAL
Table 1 - General Data
Boiler Size RS 3/100 RS 3/125
Boiler Input
MINIMUM kW (Btu/h) 29.8 ( 101 800) 37.5 (128 000)
Gas Consumption l/s (ft.
3
/h) 0.77 (98) 0.97 (123)
MID kW (Btu/h) 33.4 (113 900) 41.7 (142 400)
Gas Consumption l/s (ft.
3
/h) 0.86 (110) 1.08 (137)
MAXIMUM kW (Btu/h) 36.9 (125 800) 45.1 (153 800)
Gas Consumption l/s (ft.
3
/h) 0.95 (121) 1.17 (148)
Boiler Output to Water
MINIMUM kW (Btu/h) 23.4 (80 000) 29.3 (100 000)
MID kW (Btu/h) 26.4 (90 000) 33.0 (112 5000)
MAXIMUM kW (Btu/h) 29.3 (100 000) 35.8 (122 000)
Burner Setting Pressure (hot)
MINIMUM mbar (in w.g.) 8.6 (3.4) 10.8 (4.3)
MID mbar (in w.g.) 11.0 (4.4) 13.0 (5.2)
MAXIMUM mbar (in w.g.) 13.4 (5.4) 15.0 (6.0)
Flue Gas Flow Rate g/s 17.3 21.2
Flue Gas Temperature
o
C 167 163
Seasonal Efficiency (SEDBUK)* % 72.3 72.6
Table 2 - Performance Data
Note.
Gas consumption is calculated using a calorific value of
38.7 MJ/m
3
(1038 Btu/ft
3
) gross or 34.9 MJ/m
3
(935 Btu/ft
3
)
nett. To obtain the gas consumption at a different calorific
value:-
a. For l/s - divide the gross heat input (kW) by the gross
C.V. of the gas (MJ/m
3
)
b. For ft
3
/h - divide the gross heat input (Btu/h) by the gross
C.V. of the gas (Btu/ft
3
)
c. The appliance is preset at the factory to the highest
nominal rating.
Key to symbols
GB = United Kingdom IE = Ireland
(Countries of destination)
PMS = Maximum operating pressure of water
C
11
= A room sealed appliance designed for connection via
ducts to a horizontal terminal, which admits fresh air to
the burner and discharges the products of combustion
to the outside without a fan in the combustion products
circuit.
I
2H
= An appliance designed for use on 2nd Family gas,
Group H only.
*The value is used in the UK government's Standard Assessment Procedure (SAP) for energy rating of dwellings.
The test data from which it has been calculated have been certified by BGplc 0087