28: AS-INTERFACE MASTER COMMUNICATION
28-34 « FC4A MICROSMART USER’S MANUAL »
Error Messages
When an error is returned from the AS-Interface master module, WindLDR will display an error message. The error codes
and their meanings are given below.
When a reply message is not returned from the AS-Interface master module, the following error message will be dis-
played.
Error Code Description
1
• An error was found on the expansion I/O bus.
2
• While the AS-Interface master module was in offline mode, attempt was made to per form auto
configuration or manual configuration.
• An incorrect command was sent.
7
• While slave address 0 existed on the bus, attempt was made to perform auto configuration or
manual configuration.
• The AS-Interface master module is in local mode.
8
• The slave you are trying to change does not exist.
• A slave of the designated new address already exists.
• While a standard slave was set at A address, attempt was made to set an A/B slave at B
address of the same number.
• While an A/B slave was set at B address, attempt was made to set a standard slave at A
address of the same number.
• Attempt was made to change the parameters of a slave which did not exist.