FanCoils
INSTALLATION,OPERATION,&MAINTENANCEMANUAL
8
SECTIONONE—Receipt&InitialInstallation,Cont'd.
somelocationwhereanindicationofdrainowrestriction
maybereadilyobserved.Unitsfurnishedwitha“tell-tale”
connectionshouldbeslopedveryslightlytowardsthe
drainoutlets.The differential height of the trap inlet to
outlet must be at least one inch greater than the total
static pressure on the unit. The height from the drain
outlet to the bottom of the trap must not be less than
the total static pressure. The condensate drain hose
should be secured with a clamp after installing.
Ductwork Connections
Allductworkand/orsupplyandreturngrillesshould
beinstalledinaccordancewiththeprojectplansand
specications.Ifnotincludedontheunitorfurnishedfrom
thefactory,supplyandreturngrillesshouldbeprovidedas
recommendedintheproductcatalog.
Forunitswithnoreturn-airductwork,checklocalcode
requirementsforpossibleapplicationrestrictions.Allunits
mustbeinstalledinareasthatarenon-combustible.
Somemodelsaredesignedtobeconnectedtoduct-work
withaMINIMUMamountofexternalstaticpressure.
Theseunitsmaybedamagedbyoperationwithout
theproperductworkconnected.Consulttheapproved
submittalsandtheproductcatalogforunitexternalstatic
pressurelimitations.
Unitsprovidedwithoutsideairforventilationshouldhave
someformoflow-temperatureprotectiontopreventcoil
freeze-up.Thisprotectionmaybeanyofseveralmethods
suchasalow-temperaturethermostattoclosetheoutside
airdamperorapreheatcoiltotempertheoutsideair
beforeitreachestheunit.
Itshouldbenotedthatnoneofthesemethodswill
adequatelyprotectacoilintheeventofpowerfailure.
Thesafestmethodoffreezeprotectionistouseglycolin
theproperpercentsolutionforthecoldestexpectedair
temperature.
HorizontalplenumtypeCPYShortShipTime(SST)units
maybeshippedwithabottomreturn-airinlet.Theseunits
maybeconvertedtorearreturnbyremovingthebottom
inletlterretainerclipsandlter,thenremovingthe
plenumrearpanel.Therearpanelmustthenbemovedto
thebottomoftheunitandreversedsothatthetopedge
(whenrearmounted)istowardthesupplyendoftheunit
andreinstalledonthebottomoftheplenum.Thepanel
shouldbepositionedtowardsthedrainpantoexpose
theone-inchwidelterslotforunit-mountedlters.The
panelshouldbepositionedagainsttherearbottombrace
completelycoveringthebottomoftheplenumonunits
withremotelters.
Hi-Performanceplenum-typemodelsHPYSSTunitsmay
beshippedwithabottomreturn-airinlet.Theseunits
maybeconvertedtorearreturnbysimplyexchangingthe
bottomandrearplenumpanels.
Flexibleductconnectionsshouldbeusedonallair
handlingequipmenttominimizevibrationtransmissions.
Allductworkandinsulationshouldbeinstalledtoallow
properaccesstoallcomponentsforserviceandrepair
suchaslters,motor/blowerassemblies,etc.
The manufacturer assumes no responsibility for
undesirable system operation due to improper design,
equipment or component selection, and/or installation
of base unit, ductwork, grilles, and other related
components.
Electrical Connections
Theunitserialplateliststheunitelectricalcharacteristics
suchastherequiredsupplyvoltage,fanandheater
amperageandrequiredcircuitampacities.Theunitwiring
diagramshowsallunitandeldwiring.Sinceeachproject
isdifferentandeachunitonaprojectmaybedifferent,
theinstallermustbefamiliarwiththewiringdiagramand
serialplateontheunitBEFOREbeginninganywiring.
Allcomponentsfurnishedforeldinstallationbyeitherthe
factoryorthecontrolscontractorshouldbelocatedand
checkedforproperfunctionandcompatibility.Allinternal
componentsshouldbecheckedforshippingdamage,and
anylooseconnectionsshouldbetightenedtominimize
problemsduringstart-up.
Anydevicessuchasfanswitchesorthermostatsthat
havebeenfurnishedfromthefactoryforeldinstallation