49
ifm Device Manual IO-Link Master with PROFINET interface CabinetLine 8 Ports IP 20 (AL1900) 05 / 2018
Configuration IoT Core
>
8.3.10 Read information about IO-Link devices
16553
Information about an IO-Link device connected via an IO-Link port is saved in the
iolinkmaster/port[n]/iolinkdevice/ substructure. The user can access the following data
points:
iolinkmaster/port[n]/iolinkdevice/status
Status of the connected IO-Link device
0 = SENSOR_NOT_CONNECTED
1 = SENSOR_IN_PREOPERATE
2 = SENSOR_IN_OPERATE
3 = SENSOR_WRONG
iolinkmaster/port[n]/iolinkdevice/vendorid
IO-Link ID of the manufacturer
iolinkmaster/port[n]/iolinkdevice/deviceid
IO-Link ID of the IO-Link device
iolinkmaster/port[n]/iolinkdevice/productname
Product name of the IO-Link device
iolinkmaster/port[n]/iolinkdevice/serial
Serial number of the IO-Link device
iolinkmaster/port[n]/iolinkdevice/applicationspecifictag
Device-specific identification (application tag)
n ... 1...8
r ... read only
rw ... read and write