28
11 Technical data
11.1 Setting ranges
The setting ranges depend on the operating mode (→ 4.1)�
11.1.1 Setting ranges in operating mode 2
rP / SP cFL / cFH ASP / AEP
ΔP
Setting
range
Min�
distance
Setting
range
Min�
distance
Setting
range
Min�
distance
PN2160
PN2560
bar
1…600 3 0…600 3 0…600 120 1
psi
20…8700 40 0…8700 40 0…8700 1760 20
MPa
0�1…60 0�3 0…60 0�3 0…60 12 0�1
PN2070
PN2570
bar
1…400 2 0…400 2 0…400 80 0�5
psi
10…5800 30 0…5800 30 0…5800 1170 10
MPa
0�1…40 0�2 0…40 0�2 0…40 8 0�05
PN2071
PN2571
bar
0�5…250 1�5 0…250 1�5 0…250 50 0�5
psi
10…3625 15 0…3625 15 0…3625 730 5
MPa
0�05…25 0�15 0…25 0�15 0…25 5 0�05
PN2092
PN2592
bar
0�2…100 0�6 0…100 0�6 0…100 20 0�2
psi
4…1450 6 0…1450 6 0…1450 292 2
MPa
0�02…10 0�06 0…10 0�06 0…10 2 0�02
PN2093
PN2593
bar
-0�95…25 0�15 -1…25 0�15 -1…25 5 0�05
psi
-13�5…362�5 1�5 -14�5…362�5 1�5 -14�5…362�5 73 0�5
MPa
-0�095…2�5 0�015 -0�1…2�5 0�015 -0�1…2�5 0�5 0�005
ΔP = step increment