4 Installation
Using process adapters the unit can be adapted to different process connections�
• Adapters have to be ordered separately as accessories�
A correct fit of the unit and ingress resistance of the connection are only en-
sured using ifm adapters�
• For small flow rates ifm adapter blocks are available�
4.1 Installation location
General

•The sensor tip is to be completely sur-
rounded by the medium�
•Immersion depth of the sensor: mini-
mum 12 mm�
Recommended
•For horizontal pipes: mounting from
the side�
•For vertical pipes: mounting in the rising
pipe�
Conditional
•Horizontal pipe / mounting from the bot-
tom: if the pipe is free from build-up�
•Horizontal pipe /mounting from the
top: if the pipe is completely filled with
medium�
To be avoided
•The sensor tip must not be in contact
with the pipe wall�
•Do not mount in downpipes that are
open at the bottom!