DataLink Technologies Gateways, Inc.
Website: www.datalink-networks.com Tel : (604) 632-4278 / (866) 709-6390
12
Set the baud rate of the serial console port [57600]?
9600, 19200, 38400, 57600, 115200
SECURITY SETTINGS:
Would you like to update the Root Password [N]?
Would you like to update the Administrator 'admin' Password [N]?
MISCELLANEOUS SETTINGS:
Each development board must have a unique serial number
Set the board's serial number[A00800333]?
How long (in seconds) should CPU delay before starting up [5]?
Saving the changes in NV memory...
Default Settings
DF1 protocol:
9600 Baud, 8 Bits, No Parity, BCC Checksum
DH+ defaults
57.6 KBaud
Node address: 1 octal, 0x01 hex, decimal 1
4.4 USB Driver Installation
The USB driver is provided by Future Technology Devices International Ltd. Please
see the Windows_XP_Installation_Guide.pdf in the Documentation folder on the CD
included with the GW1000. The USB driver version on the CD is “CDM 2.02.04 WHQL
Certified.” See section “2.1 Installing CDM drivers” on page 4. For reference, the
document is also available here…
http://www.ftdichip.com/Documents/InstallGuides/Windows_XP_Installation_Guide.pdf
4.5 Firmware Upgrade
Firmware upgrade is accomplished using the ethernet interface and a web browser.
Connect the GW1000 ethernet port to an ethernet port on the same network as your
PC using a CAT5 network patch cord to a network hub or router. Open a web browser
such as Microsoft Internet Explorer or Mozilla Firefox, power on the GW1000 and wait
30 seconds for bootup sequence to complete. Note the LAN LINK indicator LED
should be on.