15
4
6
5
1
3
2
7
8
5
9
7
A
S
C82
1-22
C42
C52
1-23
1-25
C82
1-24
INSTALLERUSER
MAINTENANCE TECHNICIAN
Maximum usable length
(including intake terminal with grill and two 90° bends)
NON INSULATED PIPE INSULATED PIPE
Exhaust (m) Intake (m) Exhaust (m) Intake (m)
1 36,0* 6 29,5*
2 34,5* 7 28,0*
3 33,0* 8 26,5*
4 32,0* 9 25,5*
5 30,5* 10 24,0*
* e air intake pipe can be increased to 2.5 metres if the exhaust bend is
eliminated, 2 metres if the air intake bend is eliminated, and 4.5 metres
eliminating both bends.
11 22,5*
12 21,5*
• Extension pipes and elbows push-ttings. To
install push-tting extensions with other ele-
ments of the ue extraction elements assembly,
proceed as follows: engage the pipe or elbow
with the male side (smooth) in the female
section (with lip seal) up to the stop on the
previously installed element. is will ensure
sealing eciency of the coupling.
• Installation clearances. Figure 1-22 gives the
min. installation space dimensions of the
Ø80/80 separator terminal kit in limited
conditions.
• Figure 1-23 shows the conguration with ver-
tical exhaust and horizontal intake.
• Extensions for the separator kit Ø80/80. e
max. vertical straight length (without bends)
that can be used for Ø80 intake and exhaust
pipes is 41 metres of which 40 intake and 1
exhaust. The total length corresponds to a
resistance factor of 100. e total usable length
obtained by adding the length of the intake and
exhaust pipes Ø80, must not exceed the values
stated in the following table. If mixed accesso-
ries or components are used (e.g. changing from
a separator Ø80/80 to a concentric pipe), the
maximum extension can be calculated by using
a resistance factor for each component or the
equivalent length. e sum of these resistance
factors must not exceed 100.
• Temperature loss in flue ducts. To prevent
problems of ue gas condensate in the exhaust
pipe Ø80, due to ue gas cooling through the
wall, the length of the pipe must be limited to
just 5 m. (Fig. 1-25). If longer distances must
be covered, use Ø80 pipes with insulation (see
insulated separator kit Ø80/80 chapter).
N.B.: when installing the Ø80 ducts, a section
clamp with pin must be installed every 3metres.
e kit includes:
N°1 - Exhaust gasket (1)
N°1 - Flange seal (2)
N°1 - Female intake ange (3)
N°1 - Female exhaust ange (4)
N°2 - 90° bend Ø 80 (5)
N°1 - Intake terminal Ø 80 (6)
N°2 - Internal wall sealing plates (7)
N°1 - External wall sealing plate (8)
N°1 - Exhaust pipe Ø 80 (9)
Important: if installation requires extending the ue ttings up to the exhaust a length that exceeds the 12 m recommended, it is necessary to properly
consider the possibility that condensation may form inside the duct and therefore Immergas “Serie Blu” insulated ue ttings, or other ue ttings with
similar characteristics, should be used.