EasyManua.ls Logo

Immergas VICTRIX PRO V2 EU - Page 113

Immergas VICTRIX PRO V2 EU
144 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
VICTRIX PRO V2 EU
113
1
2
Technical Notes:
- e jumper X40 must be removed.
- e Modbus parameters can be found in the 'TECHNICIAN/SYSTEM SETTINGS/Modbus parameters'
menu.
- e parameter 'Heating request type' must be set as 'Room thermostat setpoint' (default value).
- It is possible to connect the following sensors to the device and read them via BUS:
- System ow probe (B1-2);
- External probe (B4);
- DHW probe (B2);
- DHW Contact or ermostat (S50).
- e DHW can be managed locally (appropriately congure the 3-way valve via the parameters in the "Relay
settings" menu).
- BMS: a pull-up resistance and a pull-down resistance must be present on the bus.
- In the diagram, it is assumed that the two pull up and pull down resistances are already present in the external
appliance (for this reason, TR+ should not be connected with T+ and TR- with T-).
- e resistance (120 ohm) is required on both sides of the BUS (bridging between terminals 'TRD' and 'T-' and
adding the 120ohm resistance, BMS device side, is the responsibility of the installer).
Key:
A4 - Display board
A38 - Connection card (signals)
1 - Cable type: twisted pair (20 / 22 AWG)
2 - BMS (modbus master) (optional)
26.18 WIRING DIAGRAM: CONNECTION TO BMS SYSTEM

Related product manuals