VICTRIX PRO V2 EU
117
27.2 TECHNICAL DATA
Adjustable central heating temperature °C 15-90 15-90 15-90
System max. working temperature °C 95 95 95
System max. working pressure bar 6 6 6
Head available with 2400 l/h ow rate kPa (m c.a.) 101,0 (10,1) 117,0 (11,7) 117,0 (11,7)
Gas ow rate at METHANE burner (G20) m
3
/h
from 1,24 - to 12,12 from 3,07 - to 14,92 from 3,67 - to 18,0
Gas ow rate at LPG burner (G31) kg/h
from 0,91 - to 8,89 from 2,25 - to 10,95 from 2,70 -to 13,2
Useful heat output at Pn (η100)
ref. UNI EN 15502-1
% 109,2 108,5 108,4
Useful heat output at Pn (η30)
ref. UNI EN 15502-1
% 98,0 97,7 98,2
Electric power supply V/Hz 230 - 50 230 - 50 230 - 50
Nominal power absorption A 3 3.2 2.8
Installed electric power W 410 580 520
Fan max absorbed power W 220 247 200
Pump max absorbed power W 175 258 298
Power absorbed in stand-by W 6 6.5 6
Electric insulation rating IP X5D X5D X5D
Boiler water content litres 10.0 12.0 15.0
Weight of empty boiler kg 101 112 148
VICTRIX PRO
V2 120 EU
VICTRIX PRO
V2 150 EU
VICTRIX PRO
V2 180 EU
Maximum nominal heat input kW 114,5 141,0 170.0
Maximum nominal heat input
gas 20% H2NG
kW 109.0 131,3 160,6
Min. heat input kW 11.7 29.0 34.7
Min. gas heat input 20% H2NG kW 11.0 27.5 32.9
Maximum useful heat output (80/60°C) kW 112.3 138.3 166,9
Maximum useful heat output (80/60°C)
gas 20% H2NG
kW 106.9 128,8 157.7
Min. useful heat output (80/60°C) kW 11.3 28.3 33.8
Min. useful heat output (80/60°C) gas 20%
H2NG
kW 10.6 26.8 32,1
Maximum useful heat output (50/30°C) kW 121,7 149,9 180,2
Maximum useful heat output (40/30°C) kW 124.1 151,2 182.8
Eciency at nominal heat output (80/60°C) % 98.1 98.1 98.2
Eciency at nominal heat output (50/30°C) % 106.3 106.3 106.0
Eciency at nominal heat output (40/30°C) % 108.4 107.2 107.5
Eciency at min. heat output (80/60°C) % 96.5 97.6 97.5
Eciency at min. heat output (50/30°C) % 107.6 108.1 108.2
Eciency at min. heat output (40/30°C) % 108.9 108.8 108.6
Technical note
e minimum and maximum head data (Pa) of the fan are displayed on pages 88 and 89