26
Register
Address:
Decimal
[hex]
Class & Type Function: Binary Format:
40839
[0346]
Class: AlarmStatus
Type: Read-only
Days since
asserting Total
tap changes
alarm
dddddddddddddddd
“d” = 10ths of a day
40840
[0347]
Class: AlarmStatus
Type: Read-only
Days since
asserting Low
tap alarm
dddddddddddddddd
“d” = 10ths of a day
40841
[0348]
Class: AlarmStatus
Type: Read-only
Days since
asserting High
tap alarm
dddddddddddddddd
“d” = 10ths of a day
40842
[0349]
Class: AlarmStatus
Type: Read-only
Days since Low
draghand hit
new extremum
dddddddddddddddd
“d” = 10ths of a day
40843
[034A]
Class: AlarmStatus
Type: Read-only
Days since High
draghand hit
new extremum
dddddddddddddddd
“d” = 10ths of a day
40865
[0360]
Class:
AlarmClearing,
StatisticsResetting
Type:
Write-only,
Write 0 to clear
On-tap reset 000000000000000s
LSB (s)
0 = reset
1 = ignored
40869
[0364]
Class:
AlarmClearing,
StatisticsResetting
Type:
Write-only,
Write 0 to clear
Up-to/down-to
reset
000000000000000s
LSB (s)
0 = reset
1 = ignored
40870
[0365]
Class:
AlarmClearing,
StatisticsResetting
Type:
Write-only,
Write 0 to clear
Pass-through-
neutral reset
000000000000000s
LSB (s
)
0 = reset
1 = ignored
41025
[0400]
Class: state
Type:
Read-only
Analog output 0000aaaaaaaaaaaa
12-bit number (in binary)