3 Page 3 - 8 TS-LLD INSTALLATION GUIDE
Frequently Asked Questions (Continued... )
How do I Start a Manual Test ?
See this Chapter about using the RESET-TEST button to Start a 0.1 gph Annual
Precision Leak Test (also see the test Requirements before you start it).
How Often Should the Manual Test be Run ?
See Chapter 4 about Line Leak Detection and INCONs recommended frequency
(the manual test cannot be started when a flashing 84 error code is displayed).
What Should I Do:
When a 3 gph Leak Test Fails / Gross Leak is Detected ?
The display shows a flashing
3
Alarm code —
i
mmediately follow the
instructions in Chapter 4
When a 0.2 gph Leak Test Fails / Leak is Detected ?
The display shows a flashing
2
Alarm code —
follow the instructions in
Chapter 4
When a 0.1 gph Annual Precision Leak Test Fails / Leak is Detected ?
The display shows a flashing
1
Alarm code — follow the instructions in Chapter 4
Visually inspect the sump and dispenser areas whenever the TS-LLD reports
a leak !
—
❖
—
!