Troubleshooting Guide Page 6.2 - 3 6.2
Problem Description/Symptom Probable Cause (Action to take)
Can’t Dispense Flashing 83 Error Code
No communications between LSU
and CU
(New installations: Check for loose wiring, or
wiring errors, or omissions )
Previously functioning systems — Press
RESET to allow dispensing for another 4
hours and call INCON Tech Service)
Can’t Dispense Flashing 84 Error Code
The line is Out-of-Compliance because
a Monthly Compliance Test has not
passed in the last 33 days)
(This Error Code cannot be reset by pressing
the RESET TEST button — product dis-
pensing is not allowed when Out of
Compliance. A new 0.2 gph test automati-
cally starts when this Error is displayed.
Prevent dispensing and give the test time to
finish { from 13 minutes to 4 hours later }.
This may happen in extremely busy stations.
Are the turbines turned-off after hours ?
Ask the station to keep the circuit breakers /
turbines on so tests can finish after hours.
Call INCON if the Leak Test does not finish.
A valve seat may have failed at the LSU
which would cause indeterminate test result
(neither pass or fail), and will cause the days
to count up. )
Can’t Dispense Flashing 85 Error Code
The LSU requires service.
(Press RESET to allow dispensing for
another 4 hours. Schedule service when this
error occurs repeatedly.
See Chapters about Safety, Installation,
Maintenance and Testing and call INCON)
Please call our service department for tips and solutions to other problems not addressed at
the time of this publication. Also, call INCON technical service when warnings, alarms, or
error codes happen often or repeat often. Also, see Chapter 6.0 before calling INCON.