EasyManua.ls Logo

INFOSEC UPS SYSTEM E3 PERFORMANCE RT Series - Page 45

INFOSEC UPS SYSTEM E3 PERFORMANCE RT Series
92 pages
Go to English
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
INFOSEC UPS SYSTEM - 15, rue du Moulin - 44880 Sautron - FRANCE - www.infosec-ups.com
Hot Line Tel + 33 (0)2 40 76 15 82 - Fax + 33 (0)240 94 29 51 - hotline@infosec.fr – 06 17 AA 59 205 05

Steps for setting programmable outlet
Step 1:
Before entering setting mode, the UPS should be in Stand-by
mode (off-charging) and make sure the battery is connected.
The LCD display is shown as right.
Step 2:
Press and hold the “SELECT button for 3 seconds to enter
Setting mode.
Step 3:
Press the “Up button (ON/MUTE) to switch to "02" of program
list. Then press “Enter” button to enter value setting of
parameter 2. Press the “Up” button to validate the value to
“ENA to enable the programmable outlet function. Then press
“Enter” button again to confirm the setting.
Step 4:
Press the “Up button (ON/MUTE) again to switch to "03" of
program list. Then press “Enter” button for setting
programmable outlet time. Push Up” button to change the value
of backup time according your demand. Then press “Enter” to
confirm the setting.
Step 5:
Press Up button (ON/MUTE) to switch to "00" of program list. Then press “Enter” button to exit setting
menu.
Step 6:
Disconnect AC input and wait until the LCD display is off. The new setting will be activated when
turning on the UPS again.

Related product manuals