EasyManua.ls Logo

INFOSEC UPS SYSTEM E3 PERFORMANCE RT Series - 06: Autonomy limitation setting; 07: Battery total AH setting; 08: Dry contact EPO logic setting

INFOSEC UPS SYSTEM E3 PERFORMANCE RT Series
92 pages
Go to English
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
INFOSEC UPS SYSTEM - 15, rue du Moulin - 44880 Sautron - FRANCE - www.infosec-ups.com
Hot Line Tel + 33 (0)2 40 76 15 82 - Fax + 33 (0)240 94 29 51 - hotline@infosec.fr – 06 17 AA 59 205 05

06: Autonomy limitation setting
Interface
Setting
Parameter 2 : Set up backup time on battery mode for general
outlets.
0-999: setting the backup time in minutes from 0-999 for
general outlets on battery mode.
DIS: Disable the autonomy limitation and the backup time will
depend on battery capacity. (Default)
Note: When setting as “0”, the backup time will be only 10
seconds.
07: Battery total AH setting
Interface
Setting
Parameter 2 : Set up the battery total AH of the UPS.
7-999: setting the battery total capacity from 7-999 in
AH. Please set the correct battery total capacity if
external battery bank is connected.
08: Dry contact EPO logic setting
Interface
Setting
Set up the EPO function control logic.
AO: Active Open (Default). When AO is selected as EPO
contact logic, it will activate EPO function with Pin 1 and Pin 2
in open status.
AC: Active Close. When AC is selected as EPO logic, it will
activate EPO function with Pin 1 and Pin 2 in close status.
00: Exit setting

Related product manuals