26 Events
Telephone communicator
Some of the events listed above have actions which are programmed at default.
Telephone line
trouble
Fault
when the presence of the
telephone line is no longer
detected
when the presence of the
telephone line is detected
Yes Yes
SIM Error Fault
when the presence of a GMS SIM
is not detected
when the presence of a GMS
SIM is detected
Yes Yes
Insufficient SIM
Credit
Fault
when the remaining credit is less
than the programmed threshold
when the remaining credit is
more than the programmed
threshold
Yes Yes
GSM trouble Fault
when the communicator fails to
connect to the GSM network or
the signal is weak
when the communicator
connects properly to the GSM
network
Yes Yes
Mobile data network
trouble
Fault
when the SIM is not enabled for
data traffic or the communicator
cannot connect to the data
network
when the communicator
connects to the data network
Yes Yes
Communications
cancelled
Generic
when communications in progress
are cancelled
Yes No
Communications
enabled/disabled
Generic
when communications are
disabled
when communications are
enabled
Yes No
Communication
started
Generic at the start of a communication Yes No
Communication
confirmed
Generic
on confirmation of receipt of a
communication
Yes No
Failed
communication
Generic
when a communication is not
confirmed (if the communicator is
programmed to request
confirmation)
Yes No
Contact supervision
trouble
Fault
when the periodic test
communication is not confirmed
by a supervised telephone contact
when all supervised
telephone contacts confirm
receipt of a communication
Yes No
Code 0 diagnostic
information
Diagnostics
when the presence of diagnostic
information is detected
Yes No
Code 1 diagnostic
information
Diagnostics
when the presence of diagnostic
information is detected
when the presence of
diagnostic information is
detected
Yes No
Event Type Activates… Restores... Events log
Activate
actions
Event Output Contacts Voice calls SMS text message
Contact
ID event
SIA-IP/
IP2RX
event
ALARM CALL Input activation
None
Contacts #1 and
#2
“Fire alarm” “Fire alarm” 110 FA
FAULT CALL Input activation
None
Contacts #1 and
#2
“Fire system
trouble”
“Fire system fault” 300 FT
Interconnection fault activation
None
Contacts #1 and
#2
“Fire system
trouble”
“Interconnection fault” 380 FT
Interconnection fault
activation/
restore
OUT1 None None Empty None None
Battery fault
activation/
restore
None
Contacts #1 and
#2
None
“Battery trouble”/
“Restore battery trouble”
309 YT / YR
No battery
activation/
restore
None
Contacts #1 and
#2
None
“Missing battery”/
“Restore missing battery”
311 YM / YR
Power supply fault
activation/
restore
None
Contacts #1 and
#2
None
“Power supply trouble” /
“Restore power supply
trouble”
300 YP / YQ
Mains failure
activation/
restore
None
Contacts #1 and
#2
None
“Mains fault” / “Restore
mains fault”
301 AT / AR
Ground fault
activation/
restore
None
Contacts #1 and
#2
None
“Ground fault” / “Restore
ground fault”
310 UT / UR