Page #25 background image
Events 25
Installation and User manual
Appendix A
EVENTS
The events managed by the communicator are listed in the table below.
The “Events log” column indicates whether the event activation and event
restored data is recorded in the events log.
The “Activate Actions” column indicates whether the communicator can be
programmed to trigger an action when the event occurs.
The “Restores...” column is empty for non-resettable events.
Event Type Activates… Restores... Events log
Activate
actions
ALARM CALL Input Alarm
on activation of the ALARM CALL
input
on restore of the ALARM
CALL input
Yes Yes
FAULT CALL Input Fault
on activation of the FAULT CALL
input
on restore of the FAULT CALL
input
Yes Yes
IO1 Input Generic on activation of input IO1 on restore of input IO1 Yes Yes
IO2 Input Generic on activation of input IO2 on restore of input IO2 Yes Yes
IO3 Input Generic on activation of input IO3 on restore of input IO3 Yes Yes
Output Generic on activation of an output terminal
on restore of an output
terminal
Yes No
Interconnection fault Fault
when a supervised terminal is
shorted or open
when no terminal is in fault
status
Yes Yes
Battery trouble Fault
when the battery is inefficient,
discharged or short-circuited
when the battery has no
problems
Yes Yes
Missing battery Fault when the battery is disconnected
when the battery is
connected
Yes Yes
Power supply trouble Fault
when the power supply is absent,
overloaded or overheated
when the power supply is
free of problems
Yes Yes
Mains fault Fault when the mains supply fails
when the mains supply
restores
Yes Yes
Ground fault Fault
when leakage to ground is
detected
when leakage to ground is no
longer detected
Yes Yes
Data corruption Fault
when the programming data is
corrupted
when the programming data
is valid
Yes Yes
System restart Fault
when the communicator is
restarted
Yes Yes
Rearm Generic when the communicator rearms Yes Yes
Factory default Generic
when programming restores to
factory default data
Yes No
Programming Generic
at the start of a programming
session
on exiting a programming
session
Yes No
Changed date/time Generic
when the communicator date/time
is refreshed
Yes Yes
PIN entered Generic
when a user/installer PIN is
recognized
Yes Yes
Wrong PIN Generic when a wrong PIN is entered Yes Yes