EasyManuals Logo

INIM Electronics SmartLine020-2 User Manual

INIM Electronics SmartLine020-2
72 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #68 background imageLoading...
Page #68 background image
68 Iris devices
Conventional fire detection control panel
Appendix A
Iris devices
All Enea series devices manufactured by INIM Electronics for
addressable-analogue detection are LPCB certified and carry the CE
mark in compliance with the CPD standard.
The operating parameters of detectors may be modified to suit their specific environments and, when used
in conjunction with the EITK-DRV supplied by INIM Electronics. This device allows you to connect directly to
the detector line for a complete diagnosis of each detector and thus test its operating capacity, verify its
real-time values, view the contamination level in the optical smoke chamber and change its sensitivity and
operating mode. Each detector has a non-volatile memory which allows you to view the smoke and
temperature levels measured in the period prior to the last alarm detected.
The Iris series of INIM Electronics provides three conventional detector models:
Optical chamber with sealed upper-part and 500 micron hole-diameter mesh insect screen
Bicolour LED: red for alarm, green blinking for standby or for trouble
Drift compensation for sensor drift caused by dust in the chamber
Sensitivity selection for smoke and heat thresholds
Operating mode selection (for ID300 version): only smoke, only heat
AND mode, OR mode, PLUS mode
Complete diagnostics - provides contamination level and real-time values
Memory of the smoke and temperature levels measured in the five-minute period prior to the last alarm
detected
Bypass plate on base guarantees line continuity in the event of removal of the detector
For further details regarding the precise features and technical specification of each device, refer to the
respective instructions booklet.
Type Model Description
Detectors ID100 Optic smoke detector
ID200 Heat detector
ID300 Smoke and heat detector
Bases EB0010 Mounting base
EB0020 Relay base
ESB010 Sounder base (to be installed under EB0010 mounting base with
a dedicated wiring)
ESB020 Sounder base and beacon (these are to be installed under
EB0010 base and require dedicated wiring)
Manual call
points
IC0010 Manual call point
IC0010E Manual call point for outdoor installation (IP67)
Alarm repeater FI100 Remote addressable alarm repeater
Driver EITK1000 Kit for the configuration, maintenance and diagnostics of systems
using IRIS and ENEA series devices
EITK-DRV Driver for zones with IRIS series devices or loops with ENEA
series devices
EITK-BASE Base for the connection of IRIS and ENEA series detectors
EITK-PWSP Power supply for the EITK-DRV driver

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the INIM Electronics SmartLine020-2 and is the answer not in the manual?

INIM Electronics SmartLine020-2 Specifications

General IconGeneral
BrandINIM Electronics
ModelSmartLine020-2
CategoryControl Panel
LanguageEnglish

Related product manuals