The response time delay refers to the interval from the time when the inverter finishes receiving the
data to the time when it sends the data to the upstream device. If the response time delay is shorter
than the processing time of the system, it is subject to the latter; if the response time delay is longer
than the latter, it will be still in the waiting status after the data are processed by the system, and will
not send the data to the upstream device until it is up to the response time delay.
F7-04 Communication timeout
Default 0.0
Setting range 0.0 (invalid), 0.1s ~ 100.0s
When the function code is set at 0.0 s, the communication timeout time parameter is invalid.
When it is set as valid value, if the interval between a communication and the next one surpasses
the communication timeout time, the inverter deems that communication fault occurs (Err16). In
general, it is set at invalid. Setting this parameter in the continuous communication system may
monitor the communication status.
FF Group: Manufacturer Parameter (reserved)
Note: The manufacturer parameter maintains the important parameter information on the
inverter. The inverter cannot run normally or may be damaged permanently resulting from
the unauthorized modification of such parameters, it is strongly recommended that the user
shall not attempt to enter into the manufacturer parameter area.
FP Group: User Password
FP-00 User password
Default 0
Setting range 0 ~ 65535
When the password is set as any non-zero number, the password protection function is enable.
0000: Remove user password set previously, and the password protection function is invalid.
Upon the setting and validation of user password, enter the parameter setting status again, it will
prompt you to enter the user password. You cannot view and modify the parameter if the user
password is incorrect. Remember the user password.
FP-01 Parameter initialization
Default 0
0 No operation
1 Recover the default
Setting
range
2 Clear the fault records
1: The inverter will restore all the parameters to the default value.
2: The inverter will remove the latest fault records.