Function Code Table
MD380 User Manual
- 102 -
Function
Code
Parameter Name
Setting Range
Default Property
Group F6: Start/Stop Control
F6-00 Startup mode
0: Direct startup
1: Catching a spinning motor
2: Pre-excited startup (AC
asynchronous motor)
0 ƿ
F6-01
Mode of catching a spinning
motor
0: From stop frequency
1: From zero speed
2: From maximum frequency
0 ƾ
F6-02
Speed of catching a spinning
motor
1–100
20 ƿ
F6-03 Startup frequency
0.00–10.00 Hz
0.00 Hz ƿ
F6-04
Startup frequency active
time
0.0–100.0s
0.0s ƾ
F6-05
DC injection braking 1 level/
Pre-excitation level
0%–100%
0% ƾ
F6-06
DC injection braking 1 active
time/Pre-excitation active
time
0.0–100.0s
0.0s ƾ
F6-07
Acceleration/Deceleration
mode
0: Linear acceleration/
deceleration
1: S-curve acceleration/
deceleration A
0 ƾ
F6-08
Time proportion of S-curve
start segment
0.0% to (100.0% - F6-09)
30.0% ƾ
F6-09
Time proportion of S-curve
end segment
0.0% to (100.0% - F6-08)
30.0% ƾ
F6-10 Stop mode
0: Decelerate to stop
1: Coast to stop
0 ƿ
F6-11
DC injection braking 2
frequency threshold
0.00 Hz to maximum frequency
0.00 Hz ƿ
F6-12
DC injection braking 2 delay
time
0.0–100.0s
0.0s ƿ
F6-13 DC injection braking 2 level
0%–100%
0% ƿ
F6-14
DC injection braking 2 active
time
0.0–36.0s
0.0s ƿ
F6-15 Braking use ratio
0%–100%
100% ƿ
efesotomasyon.com