MD380 User Manual Desc
ription of Function Codes
- 151 -
Function Code Parameter Name Setting Range Default
F0-27
Binding command
source to
frequency source
8QLWVGLJLW%LQGLQJRSHUDWLRQSDQHO
command to frequency source)
000
0: No binding
1: Digital setting frequency
2: AI1
3: AI2
4: AI3
5: Pulse reference (DI5)
6: Multi-reference
7: Simple PLC
8: PID
9: Communication reference
Ten's digit (Binding terminal command to
frequency source)
Same as unit's digit
Hundred's digit (Binding communication
command to frequency source)
Same as unit's digit)
It is used to bind the three running command sources with the nine frequency sources,
facilitating to implement synchronous switchover.
For details on the frequency sources, see the description of F0-03 (Main frequency source X
selection). Different running command sources can be bound to the same frequency source.
If a command source has a bound frequency source, the frequency source set in F0-03 to
F0-07 no longer takes effect when the command source is effective.
Function Code Parameter Name Setting Range Default
F0-28
Serial port communication
protocol
0: Modbus protocol
3UR¿EXV'3QHWZRUNEULGJH
2: CANopen network bridge
0