MD380 User Manual Desc
ription of Function Codes
- 195 -
If the output frequency of the AC drive is within the positive and negative amplitudes of the
DQ\IUHTXHQF\UHDFKLQJGHWHFWLRQYDOXHWKHFRUUHVSRQGLQJ'2EHFRPHV21
The MD380 provides two groups of any frequency reached detection parameters, including
IUHTXHQF\GHWHFWLRQYDOXHDQGGHWHFWLRQDPSOLWXGHDVVKRZQLQWKHIROORZLQJ¿JXUH
Figure 6-21 Any frequency reaching detection
Running frequency
2))
Any frequency reached
GHWHFWLRQVLJQDO'2RUUHOD\
2)) 2))
21 21
Time
Any frequency reached
Frequency reached
detection amplitude
Frequency reached
detection amplitude
Function Code Parameter Name Setting Range Default
F8-34 Zero current detection level
0.0%–300.0% (rated
motor current)
5.0%
F8-35 Zero current detection delay time 0.00–600.00s 0.10s
If the output current of the AC drive is equal to or less than the zero current detection level
DQGWKHGXUDWLRQH[FHHGVWKH]HURFXUUHQWGHWHFWLRQGHOD\WLPHWKHFRUUHVSRQGLQJ'2
EHFRPHV217KH]HURFXUUHQWGHWHFWLRQLVVKRZQLQWKHIROORZLQJ¿JXUH
Figure 6-22 Zero current detection
2XWSXWFXUUHQW
F8-34 (Zero current
detection level)
Zero current
detection signal
Time
Time
F8-35
(Zero current
detection delay)