Description of Function Codes
MD380 User Manual
- 196 -
Function Code Parameter Name Setting Range Default
F8-36
2XWSXWRYHUFXUUHQW
threshold
0.0% (no detection)
0.1%–300.0% (rated motor current)
200.0%
F8-37
2XWSXWRYHUFXUUHQW
detection delay time
0.00–600.00s 0.00s
If the output current of the AC drive is equal to or higher than the overcurrent threshold and
WKHGXUDWLRQH[FHHGVWKHGHWHFWLRQGHOD\WLPHWKHFRUUHVSRQGLQJ'2EHFRPHV217KH
RXWSXWRYHUFXUUHQWGHWHFWLRQIXQFWLRQLVVKRZQLQWKHIROORZLQJ¿JXUH
)LJXUH2XWSXWRYHUFXUUHQWGHWHFWLRQ
Time
Time
2XWSXW
current
F8-36 (2XWSXW
overcurrent threshold)
2XWSXWRYHUFXUUHQW
detection signal
F8-37 (2XWSXWRYHUFXUUHQW
detection delay time)
Function Code Parameter Name Setting Range Default
F8-38 Any current reaching 1 0.0%–300.0% (rated motor current) 100.0%
F8-39
Any current reaching 1
amplitude
0.0%–300.0% (rated motor current) 0.0%
F8-40 Any current reaching 2 0.0%–300.0% (rated motor current) 100.0%
F8-41
Any current reaching 2
amplitude
0.0%–300.0% (rated motor current) 0.0%
If the output current of the AC drive is within the positive and negative amplitudes of any
FXUUHQWUHDFKLQJGHWHFWLRQYDOXHWKHFRUUHVSRQGLQJ'2EHFRPHV21
The MD380 provides two groups of any current reaching detection parameters, including
FXUUHQWGHWHFWLRQYDOXHDQGGHWHFWLRQDPSOLWXGHVDVVKRZQLQWKHIROORZLQJ¿JXUH