MD380 User Manual EMC
- 253 -
AC Drive
Model
Power
Capacity (kVA)
Rated Input
Current (A)
AC Input Filter Model
(Changzhou Jianli)
AC Input Filter Model
(Schaffner)
MD380T220 280 430 DL-600EBK3 FN 3270H-600-99
MD380T250 355 468 DL-600EBK3 FN 3270H-600-99
MD380T280 396 525 DL-600EBK3 FN 3270H-600-99
MD380T315 445 590 DL-600EBK3 FN 3270H-600-99
MD380T355 500 665 DL-700EBK3 FN 3270H-800-99
MD380T400 565 785 DL-800EBK3 FN 3270H-800-99
MD380T450 630 883 DL-100EBK5 FN 3270H-1000-99
Three-phase 690 V, 50/60 Hz
MD380-7T55 84 70 DL-100EBK5-CHV -
MD380-7T75 107 90 DL-100EBK5-CHV -
MD380-7T90 125 105 DL-130EBK51-CHV -
MD380-7T110 155 130 DL-160EBK5-CHV -
MD380-7T132 192 170 DL-200EBK5-CHV -
MD380-7T160 231 200 DL-250EBK31/60 -
MD380-7T200 250 235 DL-250EBK31/60 -
MD380-7T220 280 247 DL-250EBK31/60 -
MD380-7T250 355 265 No recommendation -
MD380-7T280 396 305 No recommendation -
MD380-7T315 445 350 No recommendation -
MD380-7T355 500 382 No recommendation -
MD380-7T400 565 435 DL-600EBK35/60 -
MD380-7T450 630 490 DL-600EBK35/60 -
MD380-7T500 700 595 DL-600EBK35/60 -
7.3.2 Installation of AC Input Reactor on Power Input Side
An AC input reactor is installed to eliminate the harmonics of the input current. As an optional
device, the reactor can be installed externally to meet strict requirements of an application
environment for harmonics. The following table lists the recommended manufacturers and
models of input reactors.
Table 7-2 Recommended manufacturers and models of AC input reactors
AC Drive Model
Rated Input Current
(A)
AC Input Reactor Model
(Inovance)
Three-phase power: 380–480 V, 50/60 Hz
MD380T0.7 3.4 MD-ACL-7-4T-222-2%
MD380T1.5 5 MD-ACL-7-4T-222-2%
MD380T2.2 5.8 MD-ACL-7-4T-222-2%
MD380T3.7 10.5 MD-ACL-10-4T-372-2%
MD380T5.5 14.6 MD-ACL-15-4T-552-2%
MD380T7.5 20.5 MD-ACL-30-4T-113-2%