EMC
MD380 User Manual
- 254 -
AC Drive Model
Rated Input Current
(A)
AC Input Reactor Model
(Inovance)
MD380T11 26 MD-ACL-30-4T-113-2%
MD380T15 35 MD-ACL-40-4T-153-2%
MD380T18.5 38.5 MD-ACL-40-4T-153-2%
MD380T22 46.5 MD-ACL-50-4T-183-2%
MD380T30 62 MD-ACL-80-4T-303-2%
MD380T37 76 MD-ACL-80-4T-303-2%
MD380T45 92 MD-ACL-120-4T-453-2%
MD380T55 113 MD-ACL-120-4T-453-2%
MD380T75 157 MD-ACL-200-4T-753-2%
MD380T90 180 MD-ACL-200-4T-753-2%
MD380T110 214 MD-ACL-250-4T-114-2%
MD380T132 256 MD-ACL-330-4T-164-2%
MD380T160 307 MD-ACL-330-4T-164-2%
MD380T200 385 MD-ACL-490-4T-224-2%
MD380T220 430 MD-ACL-490-4T-224-2%
MD380T250 468 MD-ACL-490-4T-224-2%
MD380T280 525 MD-ACL-660-4T-304-2%
MD380T315 590 MD-ACL-660-4T-304-2%
MD380T355 665 MD-ACL-800-4T-384-2%
MD380T400 785 MD-ACL-800-4T-384-2%
MD380T450 883 MD-ACL-1000-4T-454-2%
Three-phase power: 690 V, 50/60 Hz
MD380-7T55 70 MD-ACL-80-4T-303-2%
MD380-7T75 90 MD-ACL-90-4T-373-2%
MD380-7T90 105 MD-ACL-120-4T-453-2%
MD380-7T110 130 MD-ACL-150-4T-553-2%
MD380-7T132 170 MD-ACL-200-4T-753-2%
MD380-7T160 200 MD-ACL-200-4T-753-2%
MD380-7T200 235 MD-ACL-250-4T-114-2%
MD380-7T220 247 MD-ACL-250-4T-114-2%
MD380-7T250 265 MD-ACL-330-4T-164-2%
MD380-7T280 305 MD-ACL-330-4T-164-2%
MD380-7T315 350 MD-ACL-490-4T-224-2%
MD380-7T355 382 MD-ACL-490-4T-224-2%
MD380-7T400 435 MD-ACL-490-4T-224-2%
MD380-7T450 490 MD-ACL-490-4T-224-2%
MD380-7T500 595 MD-ACL-660-4T-304-2%