1 Product Information
- 11 -
Symbol Interface Name Function Description
D1
AC drive communication
status indicator
(green)
See
"Table 1-2 Description of indicators on
the MD500-EN1 card".
D4
Ethernet/IP operation
status indicator
(green)
D7
Ethernet/IP fault indicator
(red)
NOTE
After the MD500-EN1 card is installed, J4 is on the left and J6 is on the
right when you face the RJ45 interface. The two interfaces are direction-
insensitive. Connect either of them to the PLC.
The Cat5e shielded twisted pair (STP) network cable is recommended for
operational stability.
Table 1-2  Description of indicators on the MD500-EN1 card
Indicator State Description Solution
D1 steady green Normal N/A
D1 steady o󶍽
Abnormal communication
with the AC drive
Check whether FD-00 and FD-01 is set to 9
and 3 respectively.
D4 steady o󶍽
D7 steady red
System fault
Check the following fault codes and
solutions.
D4 steady o󶍽
D7 󶍿ashing red
Waiting for obtaining IP
address
The DHCP server assigns an IP address
to the device by using BOOTP when the
expansion card is in DHCP mode.
D4 󶍿ashing green
D7 󶍿ashing red
Disconnection or timeout
Check whether the network cable is
disconnected and the master station is
running.
D4 󶍿ashing green
D7 steady o󶍽
Waiting for connecting to
the master station
Check whether the network cable
connection is normal and the master
station is running.
D4 steady green
D7 steady o󶍽
Normal connection N/A