4 Parameters Related to Communication
- 17 -
4 Parameters Related to Communication
4.1 Communication Card Type Setting
After powering on the AC drive, set FD-00 and FD-01 to 9 (baud rate: 115200 bps) and 3
(no check, 8-N-1) respectively to enable communication between the MD500-EN1 card
and the AC drive.
Parameter
No.
Parameter Name Setting range Default Meaning
FD-00 Baud rate
0:300 bps
1: 600 bps
2:1200 bps
3:2400 bps
4:4800 bps
5:9600 bps
6:19200 bps
7:38400 bps
8:57600 bps
9:115200 bps
9
Used to set the
data transmission
rate between the
communication
expansion card
and the AC drive.
FD-01 Modbus data format
0: No check (8-N-2)
1: Even parity check (8-
E-1)
2: Odd parity check (8-
O-1)
3: No check (8-N-1)
3
Used to set
the Modbus
data format
between the
communication
expansion card
and the AC drive.
4.2 IP Address Setting of MD500-EN1 Card
Communication card parameter setting for the AC drive.
Parameter No. Parameter Name Setting Range Description
FD-37
DHCP function
selection
0: Disabled
1: Enabled
Used to set the DHCP function
of the Ethernet/IP expansion
card. Enabling the DHCP function
deactivates IP address settings,
namely parameters FD-38 to FD-
41, FD-42 to FD-45, and FD-46 to
FD-49.
FD-38
to
FD-41
Expansion card IP
address
0-255
Used to set the IP address of
Ethernet/IP expansion card.