6. Description of Parameters    
- 169 -
Function Code Parameter Name Setting Range Setting
A8-02
Selection of 
action of the slave 
in point-point 
communication
000 to 111
0: No
1: Yes
Units position: whether to 
follow masters command
1
Tens position: whether to 
send fault information to 
master when a fault occurs
1
Hundreds position: whether 
to alarm when it becomes 
ofine
-
A8-03
The slave received 
data
0: Output frequency
1: Frequency reference
0
F0-02
Command source 
selection
0: Operating panel control 
(keypad & display)
1: Terminal I/O control 
2: Serial comms.
2
F0-03
Main frequency 
reference setting 
channel selection
0: Digital setting (non-
retentive at power down)
1: Digital setting (retentive 
at power down)
2: AI1
3: AI2
4: AI3
5: Pulse reference
6: Multi-reference
7: Simple PLC
8: PID reference
9: Serial comms.
9
F0-10
Max. frequency 5.00 to 500.00 Hz 50.00 Hz 
Keep the same 
setting of this 
parameter for the 
master and slave.
F0-17
Acceleration time 1 0.0 to 6500.0s  Keep the same 
setting of this 
parameter for the 
master and slave.
F0-18
Deceleration time 1 0.0 to 6500.0s Keep the same 
setting of this 
parameter for the 
master and slave.
F8-15
Droop rate 0.00 to 10.00 Hz 1.00 Hz
A0-00
Speed/Torque 
control selection
0: Speed control
1: Torque control
0