6 Options
- 112 -
Model
MD880-01S
Series
Recommended
Input IEC Cable
Speci󶍾cations
(mm
2
)
[1]
Recommended
IEC Ground
Cable (mm
2
)
Recommended
Output IEC
Cable (mm
2
)
Terminal
Width
of the
AC Drive
(mm)
Screw
Recommended
Fuse
Bussmann
Compliant with UL
Certi󶍾cation
Recommended
Contactor
Recommended
Circuit Breaker
Rated
Current
(A)
Model
Rated Current
(A)
Rated Current
(A)
MD880-
01S-0262-4
3 x 120 70 3 x 120 30.6 M12 325 FWH-325A 205 400
MD880-
01S-0314-4
3 x 150 70 3 x 150 * M12 400 FWH-400A 245 400
MD880-
01S-0383-4
3 x 185 95 3 x 185 * M12 500 FWH-500A 300 400
MD880-
01S-0441-
4(-L)
2 x (3 x 95) 95 2 x (3 x 95) * M12 600 FWH-600A 410 500
MD880-
01S-0481-
4(-L)
2 x (3 x 120) 120 2 x (3 x 120) * M12 700 FWH-700A 410 630
MD880-
01S-0538-
4(-L)
2 x (3 x 120) 120 2 x (3 x 120) * M12 800 FWH-800A 475 630
MD880-
01S-0605-
4(-L)
2 x (3 x 150) 150 2 x (3 x 150) * M12 800 FWH-800A 620 700
MD880-
01S-0673-
4(-L)
2 x (3 x 185) 185 2 x (3 x 185) * M16 1000 170M5016 620 800
MD880-
01S-0751-
4(-L)
2 x (3 x 185) 185 2 x (3 x 185) * M16 1000 170M5016 620 800
MD880-
01S-0849-
4(-L)
2 x (3 x 240) 240 2 x (3 x 240) * M16 1250 170M6017 800 1000
NOTE
Suitable for the Chinese standard. "3 x 10" indicates one three-conductor cable,
and "2 x (3 x 95)" indicates two three-conductor cables.
Use copper conductors of a proper size as main circuit cables according to the
recommended values of power cable selection in
"3.5.3 Main Circuit Terminal
Arrangement and Dimensions"
.
Selection of the earth leakage circuit breaker (ELCB)
1) The earth leakage current of the AC drive is greater than 3.5 mA, requiring
grounding protection.
2) The AC drive generates DC leakage current in protective conductors. In this case, a
time-delay B-type ELCB must be used.
When the ELCB malfunctions, you can:
– Use an ELCB of higher rated operating current or use a B-type ELCB.