6 Options                                                                                                                      
 
- 112 -
Model 
MD880-01S 
Series
Recommended 
Input IEC Cable 
Specications 
(mm
2
) 
[1]
Recommended 
IEC Ground 
Cable (mm
2
)
Recommended 
Output IEC 
Cable (mm
2
)
Terminal 
Width 
of the 
AC Drive 
(mm)
Screw
Recommended 
Fuse 
Bussmann 
Compliant with UL 
Certication
Recommended 
Contactor
Recommended 
Circuit Breaker
Rated 
Current 
(A)
Model
Rated Current 
(A)
Rated Current 
(A)
MD880-
01S-0262-4
3 x 120 70 3 x 120 30.6  M12 325  FWH-325A 205  400
MD880-
01S-0314-4
3 x 150 70 3 x 150 * M12 400  FWH-400A 245  400
MD880-
01S-0383-4
3 x 185 95 3 x 185 * M12 500  FWH-500A 300  400
MD880-
01S-0441-
4(-L)
2 x (3 x 95) 95 2 x (3 x 95) * M12 600  FWH-600A 410  500
MD880-
01S-0481-
4(-L)
2 x (3 x 120) 120 2 x (3 x 120) * M12 700  FWH-700A 410  630
MD880-
01S-0538-
4(-L)
2 x (3 x 120) 120 2 x (3 x 120) * M12 800  FWH-800A 475  630
MD880-
01S-0605-
4(-L)
2 x (3 x 150) 150 2 x (3 x 150) * M12 800  FWH-800A 620  700
MD880-
01S-0673-
4(-L)
2 x (3 x 185) 185 2 x (3 x 185) * M16 1000  170M5016 620  800
MD880-
01S-0751-
4(-L)
2 x (3 x 185) 185 2 x (3 x 185) * M16 1000  170M5016 620  800
MD880-
01S-0849-
4(-L)
2 x (3 x 240) 240 2 x (3 x 240) * M16 1250  170M6017 800  1000
 
◆
Suitable for the Chinese standard. "3 x 10" indicates one three-conductor cable, 
and "2 x (3 x 95)" indicates two three-conductor cables.
 
◆
Use copper conductors of a proper size as main circuit cables according to the 
recommended values of power cable selection in 
"3.5.3 Main Circuit Terminal 
Arrangement and Dimensions"
.
 
■
Selection of the earth leakage circuit breaker (ELCB)
1)  The earth leakage current of the AC drive is greater than 3.5 mA, requiring 
grounding protection.
2)  The AC drive generates DC leakage current in protective conductors. In this case, a 
time-delay B-type ELCB must be used.
When the ELCB malfunctions, you can: 
– Use an ELCB of higher rated operating current or use a B-type ELCB.