1 Product Information
- 17 -
Item Speci󶍾cation
Control
characteristics
Motor control
mode
V/F control
Sensorless vector control (SVC)
Feedback vector control (FVC)
Carrier frequency
400 V system:
5.5–37 kW: 4 kHz by default;
45–55 kW: 3.2 kHz by default;
75 kW: 2.5 kHz by default;
90–450 kW: 2 kHz by default
Speed range
V/F control: 1:50
SVC: 1:200
FVC: 1:1000
Speed control
accuracy
SVC: ±10%Fsl
FVC: ±0.01%
Torque response
SVC: ≤ 5 ms
FVC: ≤ 5 ms
Startup torque
SVC: 0.5 Hz/150%
FVC: 0 Hz/200%
Mechanical
data
Antivibration
performance
Compliant with GB/T 2423.10-2008
Frequency: 5–9 Hz, displacement: 7 mm
Frequency: 9–200 Hz, acceleration rate: 5.9 m/s
2
Scanning speed: 1 oct/min
Security
performance
Compliant with EN 61800-5-1
Cooling mode Forced air cooling (AF), compliant with EN 60146
Protections
Phase loss
protection
Input phase loss protection
Output phase loss protection
Overvoltage
protection
The AC drive stops when the DC voltage of the main circuit is
above 800 V.
Undervoltage
protection
The AC drive stops when the DC voltage of the main circuit is
below 350 V.
Overtemperature
protection
Protection is triggered when the inverter bridge gets
overheated.
Overload
protection
The AC drive stops after running at 150% of rated heavy-load
current for 60 seconds.
The AC drive stops after running at 110% of rated light-load
current for 60 seconds.
Overcurrent
protection
The AC drive stops when 2.5 times of rated heavy-load
current of the AC drive is exceeded.
Brake protection
Braking resistor short-circuit protection (unavailable for
models of 18.5 kW and below)
Short-circuit
protection
Output phase-to-phase short-circuit protection
Output phase-to-ground short-circuit protection