1 Product Information
 
- 17 -
Item Specication
Control 
characteristics
Motor control 
mode
V/F control
Sensorless vector control (SVC)
Feedback vector control (FVC)
Carrier frequency
400 V system:  
5.5–37 kW: 4 kHz by default;  
45–55 kW: 3.2 kHz by default;  
75 kW: 2.5 kHz by default; 
90–450 kW: 2 kHz by default
Speed range
V/F control: 1:50
SVC: 1:200
FVC: 1:1000
Speed control 
accuracy
SVC: ±10%Fsl
FVC: ±0.01%
Torque response
SVC: ≤ 5 ms
FVC: ≤ 5 ms
Startup torque
SVC: 0.5 Hz/150%
FVC: 0 Hz/200%
Mechanical 
data
Antivibration 
performance
Compliant with GB/T 2423.10-2008
Frequency: 5–9 Hz, displacement: 7 mm
Frequency: 9–200 Hz, acceleration rate: 5.9 m/s
2
 
Scanning speed: 1 oct/min
Security 
performance
Compliant with EN 61800-5-1
Cooling mode Forced air cooling (AF), compliant with EN 60146
Protections
Phase loss 
protection
Input phase loss protection 
Output phase loss protection
Overvoltage 
protection
The AC drive stops when the DC voltage of the main circuit is 
above 800 V.
Undervoltage 
protection
The AC drive stops when the DC voltage of the main circuit is 
below 350 V.
Overtemperature 
protection
Protection is triggered when the inverter bridge gets 
overheated.
Overload 
protection
The AC drive stops after running at 150% of rated heavy-load 
current for 60 seconds.
The AC drive stops after running at 110% of rated light-load 
current for 60 seconds.
Overcurrent 
protection
The AC drive stops when 2.5 times of rated heavy-load 
current of the AC drive is exceeded.
Brake protection
Braking resistor short-circuit protection (unavailable for 
models of 18.5 kW and below)
Short-circuit 
protection
Output phase-to-phase short-circuit protection 
Output phase-to-ground short-circuit protection