- 114 -
4 Parameter Description
4
Parameter
No.
Parameter Name Setting Range Default Unit
Property
Group FC: Protection function parameters
FC-00
Program control for
protection function
Bit0: Short circuit to ground
detection at power-on
Bit2: Decelerating to stop at valid
light curtain
Bit9: Mode without door open/
close limit
0 -
ā
FC-00 is used to set program control related to protection functions. Each bit of the parameter deīænes a function,
as described in the following table.
If a bit is set to 1, the function indicated by this bit is enabled; if this bit is set to 0, the function is disabled. For
details on how to view and set this parameter, see the descriptions in section 8.21.1.
The functions deīæned by the binary bits of FC-00 are described in the following table.
Bit Function Description Default
Bit0
Short circuit to ground
detection at power-on
Whether the motor is short circuited to ground is detected at
power-on. If the motor is short circuited to ground, the controller
blocks the output immediately, and reports the fault.
0
Bit1 Reserved - 0
Bit2
Ramp to stop at valid light
curtain
During normal-speed running, the elevator decelerates to stop
immediately after the light curtain acts, and then runs to the
registered destination īoor after the light curtain restores. This
function is mainly used in the case of manual door.
0
Bit9
Mode without door open/
close limit
In this mode, the door open/close limit signal is not required, and
the system automatically judges door open/close limit. The system
determines that door open limit is implemented 3s after the door
open command is output and door close limit is implemented 3s
after the door close command is output.
0
FC-01
Program control 2 for
protection function
Bit0: Overload protection
Bit1: Canceling protection at
output phase loss
Bit2: Canceling over-modulation
function
Bit4: Light curtain judgment at
door close limit
Bit5: Canceling SPI
communication judgment
Bit14: Canceling protection at
input phase loss
65 -
ā